Feed and battery charging integrated cabinet
¡ô Applications
is mainly used for 35KVA and below substation, user change, the opening and closing
¡ô System components
System by the side of the cabinet Design: integrated system consists of rectifier modules, control systems, insulation monitoring relay (optional), flash relay (optional), Buck unit, AC power distribution unit, DC feed unit and batteries composed of
AC Distribution: two AC 380V power input, automatic switching each other back.
Lightning Protection System: 8 / 20us current wave, 40KVA
battery switch: 63A / 32A
closing branches: 2-way or 4-way 16A 32A
Control branches: 4 or 6-channel 10A 16A
Flash Output: 1 (optional)
Battery: 220V systems: 18 12V65AH less battery
110V system: 9 12V65AH less battery
Dimensions: (H ¡Á W ¡Á D): 2260mm ¡Á 800mm ¡Á 600mm
1600mm ¡Á 600mm ¡Á 600mm
|